Permit Details

Status:
Final
Type:
STATE FIRE INSPECTIONS
Address:
1340 E 1ST ST
Address NEW:
1340 E 1ST ST
Apply Date:
07/14/2009
Applicant:
SIMPLEX GRINNELL L P
Description:
FIRE ALARM
Contractors:
  • SIMPLEX GRINNELL L P

Outstanding Activity Conditions

Permit Number - T09BU01033
Permit Status: Final
Permit Description: FIRE ALARM
Total Outstanding Activity Conditions - 1
Date Name
07/14/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T09BU01033
Permit Description: FIRE ALARM
Total Completed Inspections - 2
Date Description Inspector Results Comments
07/23/2009 FIRE - ALARM FINAL CSCHULTZ Approved Tested each smoke, heat, strobe, pull station, tamper switch and flow switch on fire alarm panel. Tested battery missing pulled wiring apart tested before and after, all testing was done on battery power only took 3.5 hours to finish. Found two bad strobes and placement of one smoke to close to A/C vent, all problems are corrected. When finished system was in normal status.
09/28/2009 PERMIT FINALED LJACKSON Approved