Permit: T09BU01033
Permit Details
Apply Date:
07/14/2009
Applicant:
SIMPLEX GRINNELL L P
Description:
FIRE ALARM
Contractors:
- SIMPLEX GRINNELL L P
Outstanding Activity Conditions
Permit Number - T09BU01033
Permit Status: Final
Permit Description: FIRE ALARM
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 07/14/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T09BU01033
Permit Description: FIRE ALARM
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/23/2009 | FIRE - ALARM FINAL | CSCHULTZ | Approved | Tested each smoke, heat, strobe, pull station, tamper switch and flow switch on fire alarm panel. Tested battery missing pulled wiring apart tested before and after, all testing was done on battery power only took 3.5 hours to finish. Found two bad strobes and placement of one smoke to close to A/C vent, all problems are corrected. When finished system was in normal status. |
| 09/28/2009 | PERMIT FINALED | LJACKSON | Approved |