Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/23/2009 |
FIRE - ALARM FINAL |
|
Approved |
Tested each smoke, heat, strobe, pull station, tamper switch and flow switch on fire alarm panel. Tested battery missing pulled wiring apart tested before and after, all testing was done on battery power only took 3.5 hours to finish. Found two bad strobes and placement of one smoke to close to A/C vent, all problems are corrected. When finished system was in normal status. |