Permit: T09BU01033

Parcel: 12404063A


Addresses:

1340 E 1ST ST

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
07/23/2009 FIRE - ALARM FINAL Approved Tested each smoke, heat, strobe, pull station, tamper switch and flow switch on fire alarm panel. Tested battery missing pulled wiring apart tested before and after, all testing was done on battery power only took 3.5 hours to finish. Found two bad strobes and placement of one smoke to close to A/C vent, all problems are corrected. When finished system was in normal status.