Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Apply Date:
04/01/2009
Applicant:
A 1 FIRE SPRINKLERS L L C
Description:
Install 197 fire sprinklers
Contractors:
  • A 1 FIRE SPRINKLERS L L C

Outstanding Activity Conditions

Permit Number - T09BU00478
Permit Status: Final
Permit Description: Install 197 fire sprinklers
Total Outstanding Activity Conditions - 1
Date Name
04/01/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T09BU00478
Permit Description: Install 197 fire sprinklers
Total Completed Inspections - 3
Date Description Inspector Results Comments
05/07/2009 FIRE SPKLR - OH PIPING & HYDRO CSCHULTZ Approved 200 PSI test for 2 hours Approved.
Correct upright coverage in 4 areas all by duct work, marked on plans both FD and contractors.
Need to install pressure relief valve on system.
07/24/2009 PERMIT FINALED LTHOMAS Approved
07/24/2009 FIRE SPKLR - FINAL LTHOMAS Approved

Documents

File Name Document Type  
001_SPKLR.TIF FIRE PLANS VIEW
002_SPKLR.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW