Permit: T09BU00478

Parcel: 137055310

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Permit Number - T09BU00478

Inspection Description - FIRE SPKLR - OH PIPING & HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
05/07/2009 FIRE SPKLR - OH PIPING & HYDRO Approved 200 PSI test for 2 hours Approved.
Correct upright coverage in 4 areas all by duct work, marked on plans both FD and contractors.
Need to install pressure relief valve on system.