Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/07/2009 | FIRE SPKLR - OH PIPING & HYDRO | Approved | 200 PSI test for 2 hours Approved. Correct upright coverage in 4 areas all by duct work, marked on plans both FD and contractors. Need to install pressure relief valve on system. |