Permit: T09BU00130
Permit Details
Apply Date:
01/27/2009
Applicant:
INDEPENDENT FIRE AND SAFETY L L C
Description:
KITCHEN EXHAUST HOOD FIRE SUPPRESSION SYSTEM
Contractors:
- INDEPENDENT FIRE AND SAFETY L L C
Permit Reviews
Permit Number - T09BU00130
Permit Status: Expired
Permit Description: KITCHEN EXHAUST HOOD FIRE SUPPRESSION SYSTEM
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
01/27/2009 | MECHANICAL | 01/27/2009 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T09BU00130
Permit Status: Expired
Permit Description: KITCHEN EXHAUST HOOD FIRE SUPPRESSION SYSTEM
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
01/27/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T09BU00130
Permite Description: KITCHEN EXHAUST HOOD FIRE SUPPRESSION SYSTEM
Total Outstanding Inspections - 2
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/30/2009 | FIRE - KITCHEN EXH HOOD FINAL | N/A | Denied | MAKE UP AIR FAILED TO SHUT DOWN |
04/07/2009 | MECHANICAL - FINAL | N/A | Partial Approval | IVRS - Inspection :* 1. PROVIDE SMOKE TEST ON DUCT 2. RELOCATE HINGE KIT 3. RE-WORK GREASE DUCT SO THAT GREASE WILL NOT PUDDLE SMOKE CONTAINMENT TEST OK INTERLOCK OK |