Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
Permit Number - T09BU00130
Inspection Description - MECHANICAL - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/07/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE SMOKE TEST ON DUCT 2. RELOCATE HINGE KIT 3. RE-WORK GREASE DUCT SO THAT GREASE WILL NOT PUDDLE SMOKE CONTAINMENT TEST OK INTERLOCK OK |
|
04/06/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
02/12/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HOOD APPEARS TO BE TYPE I. THE GREASE DUCT NEEDS TO BE WELDED TO THE HOOD 2) THE DUCTS AND FAN ON ROOF ARE NOT TYPE I 3) THE MAKE UP AIR UNIT NEEDS TO BE INTERLOCKED WITH THE EXHAUST FAN |
|
02/11/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |