Permit: T08OT01471
Permit Details
Apply Date:
06/19/2008
Applicant:
MAUREEN HANLON
Description:
C OF O: OFFICE
Permit Reviews
Permit Number - T08OT01471
Permit Status: Expired
Permit Description: C OF O: OFFICE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 06/19/2008 | C OF O | 06/19/2008 | COMPLETED |
Outstanding Inspections
Permit Status: Expired
Permit Number: T08OT01471
Permite Description: C OF O: OFFICE
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/12/2009 | CERTIFICATE OF OCCUPANCY | N/A | Not ready for Inspection | IVRS - Inspection :* 1) FIRE FINAL INSPECTION 2) RESTROOMS-ADA SIGNAGE 3) HANDICAP PARKING (REPAINT AREA)-SIGN TO BE AT 84" TO BOTTOM OF SIGN (MAYBE MOUNTED) ON BLDG 4) EXIT DOORS NEED LIGHTED EXIT SIGNS |
| 02/12/2009 | FIRE - FINAL | N/A | Denied | 1.) Need to have approved plans with stamps from city on site. 2.) Occupant load is over 30, all corridors shall be 1 hour rated walls and ceilings and 20 min fire rated doors self closing self latching. (IFC 1017 - 1027.17 - 1027.17.1) 3.) 120V exit signs with battery back up power shall be posted over exit doors. (IFC 1027.3) |