Inspection Status: Denied
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/12/2009 | FIRE - FINAL | Denied | 1.) Need to have approved plans with stamps from city on site. 2.) Occupant load is over 30, all corridors shall be 1 hour rated walls and ceilings and 20 min fire rated doors self closing self latching. (IFC 1017 - 1027.17 - 1027.17.1) 3.) 120V exit signs with battery back up power shall be posted over exit doors. (IFC 1027.3) |