Permit: T08OT00540
Permit Details
Apply Date:
03/07/2008
Applicant:
COMMUNITY PARTNERSHIP OF SOUTHERN ARIZONA
Description:
C OF O:OFFICE
Permit Reviews
Permit Number - T08OT00540
Permit Status: C of o
Permit Description: C OF O:OFFICE
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
03/07/2008 | C OF O | 03/07/2008 | COMPLETED |
Completed Inspections
Permit Status: C of o
Permit Number: T08OT00540
Permit Description: C OF O:OFFICE
Total Completed Inspections - 3
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/10/2008 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection :* |
03/10/2008 | CERTIFICATE OF OCCUPANCY | GDABBS | Approved | IVRS - Inspection :* |
06/24/2008 | FIRE - FINAL | DRAMIREZ | Approved | 1.) Replace the missing tiles in the galley room. 2.) Extension cords to be used temporarily only 3.) Need cover plates in closet next to the Pima Room and in the Server Room. 4.) Replace painted sprinkler head located in the janitors closet. 5.) Remove thumb-turn lock on Rear/Employee entrance door shall be removed. 6.) Opening in ceiling in the Server Room shall be covered. 7.)Missing plugs in electrical panels H-1 and H-2 located in mechanical room. 8.) Lable door "Electrical","Mechanical" room. 9.) Interpret labelling on eclectrical panels. 10.) Exit signs located in the in hall to rest rooms are obstructing sprinkler heads. 11.) Doors leading from outside the patio back into the building shall remain un-locked at all times. |