Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T08OT00540
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/23/2009 | FIRE - FINAL | Approved | Approved 1/23/09. Item #11 was appealed and approved by the Fire Marshal. |
|
06/24/2008 | FIRE - FINAL | Denied | 1.) Replace the missing tiles in the galley room. 2.) Extension cords to be used temporarily only 3.) Need cover plates in closet next to the Pima Room and in the Server Room. 4.) Replace painted sprinkler head located in the janitors closet. 5.) Remove thumb-turn lock on Rear/Employee entrance door shall be removed. 6.) Opening in ceiling in the Server Room shall be covered. 7.)Missing plugs in electrical panels H-1 and H-2 located in mechanical room. 8.) Lable door "Electrical","Mechanical" room. 9.) Interpret labelling on eclectrical panels. 10.) Exit signs located in the in hall to rest rooms are obstructing sprinkler heads. 11.) Doors leading from outside the patio back into the building shall remain un-locked at all times. |
|
03/12/2008 | FIRE - FINAL | Cancelled | IVRS - RI canceled | |
03/11/2008 | FIRE - FINAL | Not ready for Inspection | Not ready, 3/11/08. |