C OF O:RESTAURANT

Permit Reviews

Permit Number - T08OT00053
Permit Status: Expired
Permit Description: C OF O:RESTAURANT
Start Date Submittal Complete Date Status  
01/09/2008 C OF O 03/04/2008 COMPLETED Review Details

Outstanding Inspections

Permit Status: Expired
Permit Number: T08OT00053
Permite Description: C OF O:RESTAURANT
Total Outstanding Inspections - 5
Last Inspection Date Description Inspector Results Comments
HEALTH DEPT - FINAL 724-7908 N/A Not Inspected
01/10/2008 CERTIFICATE OF OCCUPANCY N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LEVER HANDLES ON REAR DOOR AND RESTROOM DOORS
2. INSTALL INSTALLATION KIT ON TRAPS UNDER SINKS AT RESTROOMS
3. INSTALL ADA SIGNAGE AT RESTROOM
4. FLUSH HANDLE MUST BE ON WIDE SIDE OF TANK AT MENS RESTROOM
01/10/2008 FIRE - FINAL N/A Not ready for Inspection 1.) Hood system inspection required.
2.) Provide portable fire ecxtinguisher for kitchen area.
01/10/2008 SIGN - FINAL N/A Not ready for Inspection SEVERAL SIGNS ON SITE
01/28/2008 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
- HOOD NOT CONSTRUCTED OF PROPER GAUGE MATERIAL
- 24 GAUGE GALVANIZED SHEETMETAL NOT APPROVED FOR TYPE 1 HOOD
- EXHAUST AND MAKE UP AIR NOT INTERLOCKED
- MAKE UP AIR INTAKE IS WITHIN 10' OF WASTE VENT
- EXHAUST FAN HAS NO GREASE CUP ON ROOF
- EXHAUST FAN NOT HINGED COULD NOT VERIFY DUCT GAUGE
- MAKE UP AIR GRILL BLOCKED OFF WITH CARDBOARD