Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
Permit Number - T08OT00053
Inspection Description - MECHANICAL - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/28/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - HOOD NOT CONSTRUCTED OF PROPER GAUGE MATERIAL - 24 GAUGE GALVANIZED SHEETMETAL NOT APPROVED FOR TYPE 1 HOOD - EXHAUST AND MAKE UP AIR NOT INTERLOCKED - MAKE UP AIR INTAKE IS WITHIN 10' OF WASTE VENT - EXHAUST FAN HAS NO GREASE CUP ON ROOF - EXHAUST FAN NOT HINGED COULD NOT VERIFY DUCT GAUGE - MAKE UP AIR GRILL BLOCKED OFF WITH CARDBOARD |