Description:
Replaced heating and cooling system.
Contractors:
  • AIR PROS INC

Outstanding Activity Conditions

Permit Number - T08ME00276
Permit Status: Expired
Permit Description: Replaced heating and cooling system.
Total Outstanding Activity Conditions - 1
Date Name
05/23/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T08ME00276
Permite Description: Replaced heating and cooling system.
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
05/27/2008 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED 3 SCREWS AT FLUE PIPE CONNECTIONS
2) 1/2" GAS PIPE IS NOT SUFFICIENT TO SUPPLY WATER HEATER AND FURNACE
3) CUT OFF SWITCH REQUIRED IF CONDENSATE DRAIN IS PLUGGED
4) RAISE CONDENSATE VENT HIGHER THAN DRAIN
5) AS INSTALLED, COOLER DAMPER CANNOT BE INSTALLED AND REMOVED
6) INSTALL DRIP LEG ON FURNACE GAS
7) TAPE WHITE WIRE BLACK OR ROMEX WHEN USED AS HOT AND NOT NEUTRAL