Permit: T08ME00276
Permit Details
Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
2017 S AVENIDA PLANETA
Address NEW:
2017 S AVENIDA PLANETA
Apply Date:
05/23/2008
Applicant:
SOSA DIEGO
Description:
Replaced heating and cooling system.
Contractors:
- AIR PROS INC
Outstanding Activity Conditions
Permit Number - T08ME00276
Permit Status: Expired
Permit Description: Replaced heating and cooling system.
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/23/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T08ME00276
Permite Description: Replaced heating and cooling system.
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/27/2008 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED 3 SCREWS AT FLUE PIPE CONNECTIONS 2) 1/2" GAS PIPE IS NOT SUFFICIENT TO SUPPLY WATER HEATER AND FURNACE 3) CUT OFF SWITCH REQUIRED IF CONDENSATE DRAIN IS PLUGGED 4) RAISE CONDENSATE VENT HIGHER THAN DRAIN 5) AS INSTALLED, COOLER DAMPER CANNOT BE INSTALLED AND REMOVED 6) INSTALL DRIP LEG ON FURNACE GAS 7) TAPE WHITE WIRE BLACK OR ROMEX WHEN USED AS HOT AND NOT NEUTRAL |