Permit: T08ME00276

Parcel: 135062090

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/27/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED 3 SCREWS AT FLUE PIPE CONNECTIONS
2) 1/2" GAS PIPE IS NOT SUFFICIENT TO SUPPLY WATER HEATER AND FURNACE
3) CUT OFF SWITCH REQUIRED IF CONDENSATE DRAIN IS PLUGGED
4) RAISE CONDENSATE VENT HIGHER THAN DRAIN
5) AS INSTALLED, COOLER DAMPER CANNOT BE INSTALLED AND REMOVED
6) INSTALL DRIP LEG ON FURNACE GAS
7) TAPE WHITE WIRE BLACK OR ROMEX WHEN USED AS HOT AND NOT NEUTRAL