Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
3439 E HAWTHORNE ST
Apply Date:
02/26/2008
Applicant:
MORANDO MINI
Description:
install of trane split a/c gas 3ton 13seer (montaño 626-215-0911)
Contractors:
  • AMERICAN HOME MAINTENANCE INC *C

Outstanding Activity Conditions

Permit Number - T08ME00096
Permit Status: Expired
Permit Description: install of trane split a/c gas 3ton 13seer (montaño 626-215-0911)
Total Outstanding Activity Conditions - 1
Date Name
02/26/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T08ME00096
Permite Description: install of trane split a/c gas 3ton 13seer (montaño 626-215-0911)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
03/14/2008 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
- CONNECT OVERFLOW SENSOR FROM CONDENSATE PUMP
- TIGHTEN ROMEX CONNECTOR ONTO POWER CORD TO FURNACE
- PLASTIC OVERFLOW SENSOR IS TOO CLOSE TO VENT CONNECTOR
- USE COPPER & RELOCATE SENSOR AWAY FROM VENT
- INSULATE ALL EXPOSED SHEETMETAL DUCT IN FURNACE CLOSET
- DO NOT USE TAPE TO SEAL VENT CONNECTOR
- VENT IS NOT REQUIRED TO BE SEALED
- SECURE THE COPPER WATER LINE FROM PUMP
- I'M THE FUTURE, USE PRIMER ON ALL PVC FITTINGS
- IDENTIFY CIRCUIT BREAKER
- PROVIDE A PERMIT FOR ELEC. SERVICE UPGRADE
- PROVIDE THE REQUIRED GFI SERVICE RECEPTACLE AT CONDENSOR
- DOUBLE WALL VENT NOT TERMINATED WITH AN APPROVED CAP AND IS INSTALLED UPSIDE DOWN

Documents

File Name Document Type  
None DOCUMENTS VIEW