Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/14/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - CONNECT OVERFLOW SENSOR FROM CONDENSATE PUMP - TIGHTEN ROMEX CONNECTOR ONTO POWER CORD TO FURNACE - PLASTIC OVERFLOW SENSOR IS TOO CLOSE TO VENT CONNECTOR - USE COPPER & RELOCATE SENSOR AWAY FROM VENT - INSULATE ALL EXPOSED SHEETMETAL DUCT IN FURNACE CLOSET - DO NOT USE TAPE TO SEAL VENT CONNECTOR - VENT IS NOT REQUIRED TO BE SEALED - SECURE THE COPPER WATER LINE FROM PUMP - I'M THE FUTURE, USE PRIMER ON ALL PVC FITTINGS - IDENTIFY CIRCUIT BREAKER - PROVIDE A PERMIT FOR ELEC. SERVICE UPGRADE - PROVIDE THE REQUIRED GFI SERVICE RECEPTACLE AT CONDENSOR - DOUBLE WALL VENT NOT TERMINATED WITH AN APPROVED CAP AND IS INSTALLED UPSIDE DOWN |