Permit: T08ME00080
Permit Details
Apply Date:
02/14/2008
Applicant:
MORANDO MINI
Description:
replacement of 5ton 13seer split gas (liang ming 520-790-6885)
Contractors:
- AMERICAN HOME MAINTENANCE INC *C
Outstanding Activity Conditions
Permit Number - T08ME00080
Permit Status: Expired
Permit Description: replacement of 5ton 13seer split gas
(liang ming 520-790-6885)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 02/14/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T08ME00080
Permite Description: replacement of 5ton 13seer split gas
(liang ming 520-790-6885)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2008 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* CONDENSOR OVERFUSED 50 AMP. IS MAX. PVC TOO CLOSE TO FURNACE VENT USE COPPER IF NECESSARY TO 6" BEYOND VENT REMOVE TAPE FROM FURNACE VENT CANNOT CHECK FITTINGS NOT REQUIRED TO BE SEALED SEAL BACK SIDE OF DUCT CONNECTIONS TIGHTEN ROMEX CONNECTOR ONTO FURNACE CORD NOTE: TAPE WOULD NOT BE AN APPROVED SEALANT ON A POSITIVE PRESSURE VENT SYSTEM. |