Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
5936 E 4TH ST
Address NEW:
5936 E 4TH ST
Apply Date:
02/14/2008
Applicant:
MORANDO MINI
Description:
replacement of 5ton 13seer split gas (liang ming 520-790-6885)
Contractors:
  • AMERICAN HOME MAINTENANCE INC *C

Outstanding Activity Conditions

Permit Number - T08ME00080
Permit Status: Expired
Permit Description: replacement of 5ton 13seer split gas (liang ming 520-790-6885)
Total Outstanding Activity Conditions - 1
Date Name
02/14/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T08ME00080
Permite Description: replacement of 5ton 13seer split gas (liang ming 520-790-6885)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
02/28/2008 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONDENSOR OVERFUSED 50 AMP. IS MAX.
PVC TOO CLOSE TO FURNACE VENT
USE COPPER IF NECESSARY TO 6" BEYOND VENT
REMOVE TAPE FROM FURNACE VENT
CANNOT CHECK FITTINGS
NOT REQUIRED TO BE SEALED
SEAL BACK SIDE OF DUCT CONNECTIONS
TIGHTEN ROMEX CONNECTOR ONTO FURNACE CORD

NOTE: TAPE WOULD NOT BE AN APPROVED SEALANT ON A POSITIVE PRESSURE VENT SYSTEM.