Permit: T08ME00080

Parcel: 127110350


Addresses:

5936 E 4TH ST

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/28/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONDENSOR OVERFUSED 50 AMP. IS MAX.
PVC TOO CLOSE TO FURNACE VENT
USE COPPER IF NECESSARY TO 6" BEYOND VENT
REMOVE TAPE FROM FURNACE VENT
CANNOT CHECK FITTINGS
NOT REQUIRED TO BE SEALED
SEAL BACK SIDE OF DUCT CONNECTIONS
TIGHTEN ROMEX CONNECTOR ONTO FURNACE CORD

NOTE: TAPE WOULD NOT BE AN APPROVED SEALANT ON A POSITIVE PRESSURE VENT SYSTEM.