Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Apply Date:
01/11/2008
Applicant:
MORANDO MINI
Description:
REPLACEMENT OF TRANE 4T SPLIT AC/GAS ( MARTINEZ-ORTIZ 884.1787)
Contractors:
  • AMERICAN HOME MAINTENANCE INC *C

Outstanding Activity Conditions

Permit Number - T08ME00022
Permit Status: Expired
Permit Description: REPLACEMENT OF TRANE 4T SPLIT AC/GAS ( MARTINEZ-ORTIZ 884.1787)
Total Outstanding Activity Conditions - 1
Date Name
01/11/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T08ME00022
Permite Description: REPLACEMENT OF TRANE 4T SPLIT AC/GAS ( MARTINEZ-ORTIZ 884.1787)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
01/25/2008 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE PROPER DESCRIPTION OF WORK
THIS UNIT NEVER HAD A/C
2. PROVIDE SECONDARY DRAIN AT AC COIL
3. PROVIDE PROPER CLEARANCE TO ALL COMBUSTIBLES FROM FLUE PIPING
4. REFRIGERATION PIPING NOT PROPERLY SECURED
5. CONDENSATE PIPING NOT PROPERLY SECURED ON EXTERIOR
6. CONDENSING UNIT NOT PROPERLY FUSED
7. PROVIDE PROPER PERMIT TO RUN ELECTRICAL TO CONDENSING UNIT
8. BREAKER AT PANEL NOT SIZED PROPERLY
9. PROVIDE R-8 INSULATION ON ALL DUCTING IN ATTIC

Documents

File Name Document Type  
None DOCUMENTS VIEW