Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
Permit Number - T08ME00022
Inspection Description - MECHANICAL - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/25/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE PROPER DESCRIPTION OF WORK THIS UNIT NEVER HAD A/C 2. PROVIDE SECONDARY DRAIN AT AC COIL 3. PROVIDE PROPER CLEARANCE TO ALL COMBUSTIBLES FROM FLUE PIPING 4. REFRIGERATION PIPING NOT PROPERLY SECURED 5. CONDENSATE PIPING NOT PROPERLY SECURED ON EXTERIOR 6. CONDENSING UNIT NOT PROPERLY FUSED 7. PROVIDE PROPER PERMIT TO RUN ELECTRICAL TO CONDENSING UNIT 8. BREAKER AT PANEL NOT SIZED PROPERLY 9. PROVIDE R-8 INSULATION ON ALL DUCTING IN ATTIC |