Permit: T08ME00022

Parcel: 118272100

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/25/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE PROPER DESCRIPTION OF WORK
THIS UNIT NEVER HAD A/C
2. PROVIDE SECONDARY DRAIN AT AC COIL
3. PROVIDE PROPER CLEARANCE TO ALL COMBUSTIBLES FROM FLUE PIPING
4. REFRIGERATION PIPING NOT PROPERLY SECURED
5. CONDENSATE PIPING NOT PROPERLY SECURED ON EXTERIOR
6. CONDENSING UNIT NOT PROPERLY FUSED
7. PROVIDE PROPER PERMIT TO RUN ELECTRICAL TO CONDENSING UNIT
8. BREAKER AT PANEL NOT SIZED PROPERLY
9. PROVIDE R-8 INSULATION ON ALL DUCTING IN ATTIC