Permit Details

Status:
Expired
Type:
DUPLEX OTHER
Address NEW:
5350 E WILLARD ST
Apply Date:
01/07/2008
Applicant:
ENGLISH PHIL
Description:
INSTALLED TWO AC GAS PACKAGE UNITS ON ROOF WITH NEW GAS LINE AND REMOVED COOLERS
Contractors:
  • BREEZE WAYS INC

Outstanding Activity Conditions

Permit Number - T08ME00010
Permit Status: Expired
Permit Description: INSTALLED TWO AC GAS PACKAGE UNITS ON ROOF WITH NEW GAS LINE AND REMOVED COOLERS
Total Outstanding Activity Conditions - 1
Date Name
01/07/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T08ME00010
Permite Description: INSTALLED TWO AC GAS PACKAGE UNITS ON ROOF WITH NEW GAS LINE AND REMOVED COOLERS
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
01/09/2008 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
- SECURE THE GAS LINES BOTH UNITS.
- SEAL THE ABANDONED GAS LINE ROOF JACK FRONT UNIT.
- SERVICE RECEPTACLES ON ROOF NOT WORKING PROPERLY.
- TEST SHOWS FRONT RECEPTACLE WITH OPEN HOT & REAR RECEPTACLE HOT/NEUTRAL REVERSED
- SEAL ALL SPOT WELDS ON TOP OF EXPOSED DUCT
- PROVIDE DRAWING APPROVED BY THE CITY OF TUCSON TO ALLOW NEW INSTALLATION OF AC EQUIPMENT ON A ROOF WHERE THERE WAS NO AC EQUIPMENT PRIOR TO THIS INSTALLATION
- GAS PRESSURE TEST NOT HOLDING ON FRONT UNIT
- REAR UNIT PRESSURE IS OK
- PROVIDE ROOF JACKS AT ELEC. PENETRATION FOR SVC RECEPTACLES. SEAL THE LEADING EDGES OF THE DUCT LINER