Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - SECURE THE GAS LINES BOTH UNITS. - SEAL THE ABANDONED GAS LINE ROOF JACK FRONT UNIT. - SERVICE RECEPTACLES ON ROOF NOT WORKING PROPERLY. - TEST SHOWS FRONT RECEPTACLE WITH OPEN HOT & REAR RECEPTACLE HOT/NEUTRAL REVERSED - SEAL ALL SPOT WELDS ON TOP OF EXPOSED DUCT - PROVIDE DRAWING APPROVED BY THE CITY OF TUCSON TO ALLOW NEW INSTALLATION OF AC EQUIPMENT ON A ROOF WHERE THERE WAS NO AC EQUIPMENT PRIOR TO THIS INSTALLATION - GAS PRESSURE TEST NOT HOLDING ON FRONT UNIT - REAR UNIT PRESSURE IS OK - PROVIDE ROOF JACKS AT ELEC. PENETRATION FOR SVC RECEPTACLES. SEAL THE LEADING EDGES OF THE DUCT LINER |