Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/09/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- SECURE THE GAS LINES BOTH UNITS.
- SEAL THE ABANDONED GAS LINE ROOF JACK FRONT UNIT.
- SERVICE RECEPTACLES ON ROOF NOT WORKING PROPERLY.
- TEST SHOWS FRONT RECEPTACLE WITH OPEN HOT & REAR RECEPTACLE HOT/NEUTRAL REVERSED
- SEAL ALL SPOT WELDS ON TOP OF EXPOSED DUCT
- PROVIDE DRAWING APPROVED BY THE CITY OF TUCSON TO ALLOW NEW INSTALLATION OF AC EQUIPMENT ON A ROOF WHERE THERE WAS NO AC EQUIPMENT PRIOR TO THIS INSTALLATION
- GAS PRESSURE TEST NOT HOLDING ON FRONT UNIT
- REAR UNIT PRESSURE IS OK
- PROVIDE ROOF JACKS AT ELEC. PENETRATION FOR SVC RECEPTACLES. SEAL THE LEADING EDGES OF THE DUCT LINER