Permit: T08EL02214
Permit Details
Apply Date:
11/26/2008
Applicant:
BOB ZACHMEIEN
Description:
ELECTRICAL RECONNECT
Outstanding Activity Conditions
Permit Number - T08EL02214
Permit Status: Final
Permit Description: ELECTRICAL RECONNECT
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 11/26/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T08EL02214
Permit Description: ELECTRICAL RECONNECT
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/02/2008 | ELECTRIC - FINAL | RCAMACHO | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1. MISSING COVER PLATES THROUGHOUT 2. SMOKE DETECTORS BEDROOM 3. 2 WIRE OUTLETS HAVE BEEN CHANGED WITH GROUND GFCI HEAD OF CIRCUIT OR REPLACE WITH 2 WIRE 4. PROVIDE PROOF REPIPE COPPER PERMIT 5. MIXED BREAKER TYPES SERVICE PANEL 6. PROVIDE PROOF PERMIT CHANGED PANEL/MANY ADDED CIRCUITS NOT SECURED, GROUNDED RISER SIZE TOO SMALL PROVIDE PROPER CLEARANCE FROM PORCH ROOF DROP REQUIRES 8' CLEARANCE FROM ROOFTOP @ PORCH 8. PROTECT ALL ROMEX UNDER 8' FROM PHYSICAL DAMAGE 9. SIEMENS PANEL WITH MIXED BREAKERS 10. REMOVE TAPE FROM WH B-VENT STOPPED INSPECTION |
| 12/02/2008 | ELECTRIC - RECONNECT | RCAMACHO | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
| 01/14/2009 | PERMIT FINALED | JWEATHER | Approved | |
| 01/14/2009 | TEP CLEARANCE - AM | JWEATHER | Approved | RECN CLEARED PER R. CAMACHO |