Permit: T08EL02214

Parcel: 119411570


Addresses:

2089 W AJO WY

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/09/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/07/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) NOTES 3 & 4 FROM PREVIOUS
01/05/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PERMITS REQUIRED NEW 200 AMP SERVICE UPGRADE
2) PERMIT REQUIRED NEW COPPER REPIPE THROUGHOUT
3) NOTES 3 FROM PREVIOUS
4) GFCI PROTECT BATH AND KITCHEN COUNTER OUTLETS
01/02/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ACCESS TO RESIDENCE
2) NO MESSAGE LEFT ON IVR
12/02/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MISSING COVER PLATES THROUGHOUT
2. SMOKE DETECTORS BEDROOM
3. 2 WIRE OUTLETS HAVE BEEN CHANGED WITH GROUND GFCI HEAD OF CIRCUIT OR REPLACE WITH 2 WIRE
4. PROVIDE PROOF REPIPE COPPER PERMIT
5. MIXED BREAKER TYPES SERVICE PANEL
6. PROVIDE PROOF PERMIT CHANGED PANEL/MANY ADDED CIRCUITS NOT SECURED, GROUNDED RISER SIZE TOO SMALL
PROVIDE PROPER CLEARANCE FROM PORCH ROOF
DROP REQUIRES 8' CLEARANCE FROM ROOFTOP @ PORCH
8. PROTECT ALL ROMEX UNDER 8' FROM PHYSICAL DAMAGE
9. SIEMENS PANEL WITH MIXED BREAKERS
10. REMOVE TAPE FROM WH B-VENT

STOPPED INSPECTION
11/28/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
RESIDENTIAL
1. NO LOCKBOX TO ACCESS CODE
2. SERVICE INSTALLED NOT TO CODE - NUMEROUS VIOLATIONS