Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/07/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NOTES 3 & 4 FROM PREVIOUS |
|
| 01/05/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PERMITS REQUIRED NEW 200 AMP SERVICE UPGRADE 2) PERMIT REQUIRED NEW COPPER REPIPE THROUGHOUT 3) NOTES 3 FROM PREVIOUS 4) GFCI PROTECT BATH AND KITCHEN COUNTER OUTLETS |
|
| 01/02/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ACCESS TO RESIDENCE 2) NO MESSAGE LEFT ON IVR |
|
| 12/02/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MISSING COVER PLATES THROUGHOUT 2. SMOKE DETECTORS BEDROOM 3. 2 WIRE OUTLETS HAVE BEEN CHANGED WITH GROUND GFCI HEAD OF CIRCUIT OR REPLACE WITH 2 WIRE 4. PROVIDE PROOF REPIPE COPPER PERMIT 5. MIXED BREAKER TYPES SERVICE PANEL 6. PROVIDE PROOF PERMIT CHANGED PANEL/MANY ADDED CIRCUITS NOT SECURED, GROUNDED RISER SIZE TOO SMALL PROVIDE PROPER CLEARANCE FROM PORCH ROOF DROP REQUIRES 8' CLEARANCE FROM ROOFTOP @ PORCH 8. PROTECT ALL ROMEX UNDER 8' FROM PHYSICAL DAMAGE 9. SIEMENS PANEL WITH MIXED BREAKERS 10. REMOVE TAPE FROM WH B-VENT STOPPED INSPECTION |
|
| 11/28/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* RESIDENTIAL 1. NO LOCKBOX TO ACCESS CODE 2. SERVICE INSTALLED NOT TO CODE - NUMEROUS VIOLATIONS |