Description:
ELECTRICAL RECONNECT

Outstanding Activity Conditions

Permit Number - T08EL02012
Permit Status: Expired
Permit Description: ELECTRICAL RECONNECT
Total Outstanding Activity Conditions - 1
Date Name
10/22/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T08EL02012
Permite Description: ELECTRICAL RECONNECT
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
10/23/2008 ELECTRIC - RECONNECT N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/23/2008 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROTECT ALL ROMEX IN LAUNDRY UNDER 7'
2) MISSING COVER PLATES LAUNDRY
3) PROVIDE PROOF PERMIT 220 ADDED TO LAUNDRY ROOM HAZARDOUS NOT TO CODE
4) REMOVE ELECTRICAL FROM STORAGE ROOMS OR PERMIT HAZARDOUS ELECTRICAL TO STORAGE AT OVERHANG STORAGE ROOMS TO CLOSE TO PROPERTY LINES
5) REMOVE ALL CIRCUITS FROM 100 AMP METER DISCONNECT
6) REMOVE ADDED ROMEX AND LIGHT FIXTURES TO REAR PORCH OR PERMIT NOT TO CODE
7) REMOVE FRONT LIGHT FIXTURE OR PERMIT, NOT TO CODE
8) PROVIDE PROOF GARAGE ENCLOSURE TO ROOM PERMITTED
9) GFCI PROTECT KITCHEN COUNTER OUTLETS AND BATHS
10) SMOKE DETECTORS BEDROOMS
11) ALL BEDROOM BARS MUST RELEASE WITHOUT TOOLS