Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
MULTI FAMILY OTHER
Address:
342 E GLENN ST
Address NEW:
342 E GLENN ST
Apply Date:
10/22/2008
Applicant:
GARCIA ARMANDO
Description:
UPGRADE: ELECTRIC TO 200 AMP

Permit Reviews

Permit Number - T08EL02007
Permit Status: Final
Permit Description: UPGRADE: ELECTRIC TO 200 AMP
Start Date Submittal Complete Date Status  
10/22/2008 ELECTRICAL 10/22/2008 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T08EL02007
Permit Status: Final
Permit Description: UPGRADE: ELECTRIC TO 200 AMP
Total Outstanding Activity Conditions - 1
Date Name
10/22/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T08EL02007
Permit Description: UPGRADE: ELECTRIC TO 200 AMP
Total Completed Inspections - 4
Date Description Inspector Results Comments
10/07/2009 ELECTRIC - SERVICE UPGRADE DSANTACR Approved IVRS - Inspection :*
1) RETURN INSPECTION-PM
2) STRAP #4 BARE WIRE (GROUND) TO WALL
3) INSTALL ROOF JACKS
4) BOND GAS PIPING
5) NO LOADS CONNECTED YET
6) CALL FOR FINAL WHEN DONE
10/08/2009 TEP CLEARANCE - AM JWEATHER Approved INCR CLEARED PER D. SANTACRUZ
10/09/2009 ELECTRIC - FINAL RMAJUTA Approved 1) WATER BOND TO WATER LINE BELOW #342 NOT TIGHTEN
2) CONCENTRIC KO DAMAGED WHERE 1" PLASTIC FLEX ENTERS NORTH SIDE OF SERVICE FOR #342 USE REDUCING WASHERS TO COVER ENTRY
3) WIRES COMING INTO THE BACK OF J-BOX BETWEEN METERS TO HAVE BUSHINGS
4) J-BOX MUST BE GROUNDED-USE BARE WIRE FROM SERVICE
02/22/2010 PERMIT FINALED JWEATHER Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW