Permit: T08EL02007
Permit Details
Apply Date:
10/22/2008
Applicant:
GARCIA ARMANDO
Description:
UPGRADE: ELECTRIC TO 200 AMP
Permit Reviews
Permit Number - T08EL02007
Permit Status: Final
Permit Description: UPGRADE: ELECTRIC TO 200 AMP
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 10/22/2008 | ELECTRICAL | 10/22/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T08EL02007
Permit Status: Final
Permit Description: UPGRADE: ELECTRIC TO 200 AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/22/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T08EL02007
Permit Description: UPGRADE: ELECTRIC TO 200 AMP
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/07/2009 | ELECTRIC - SERVICE UPGRADE | DSANTACR | Approved | IVRS - Inspection :* 1) RETURN INSPECTION-PM 2) STRAP #4 BARE WIRE (GROUND) TO WALL 3) INSTALL ROOF JACKS 4) BOND GAS PIPING 5) NO LOADS CONNECTED YET 6) CALL FOR FINAL WHEN DONE |
| 10/08/2009 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER D. SANTACRUZ |
| 10/09/2009 | ELECTRIC - FINAL | RMAJUTA | Approved | 1) WATER BOND TO WATER LINE BELOW #342 NOT TIGHTEN 2) CONCENTRIC KO DAMAGED WHERE 1" PLASTIC FLEX ENTERS NORTH SIDE OF SERVICE FOR #342 USE REDUCING WASHERS TO COVER ENTRY 3) WIRES COMING INTO THE BACK OF J-BOX BETWEEN METERS TO HAVE BUSHINGS 4) J-BOX MUST BE GROUNDED-USE BARE WIRE FROM SERVICE |
| 02/22/2010 | PERMIT FINALED | JWEATHER | Approved |