Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/19/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/09/2009 | ELECTRIC - FINAL | Denied | 1) WATER BOND TO WATER LINE BELOW #342 NOT TIGHTEN 2) CONCENTRIC KO DAMAGED WHERE 1" PLASTIC FLEX ENTERS NORTH SIDE OF SERVICE FOR #342 USE REDUCING WASHERS TO COVER ENTRY 3) WIRES COMING INTO THE BACK OF J-BOX BETWEEN METERS TO HAVE BUSHINGS 4) J-BOX MUST BE GROUNDED-USE BARE WIRE FROM SERVICE |