Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
4633 E 12TH ST
Address NEW:
4633 E 12TH ST
Apply Date:
10/08/2008
Applicant:
TERRY WINTZ
Description:
RECONNECT:ELECTRIC

Outstanding Activity Conditions

Permit Number - T08EL01935
Permit Status: Expired
Permit Description: RECONNECT:ELECTRIC
Total Outstanding Activity Conditions - 1
Date Name
10/08/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T08EL01935
Permite Description: RECONNECT:ELECTRIC
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
10/09/2008 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUND WIRE CUT OFF AND REMOVED AT SERVICE PANEL, INSTALL NEW GRD WIRE AND H20 BOND
2) NEED WORKING SMOKE DETECTORS IN EACH BEDROOM AND ONE IN HALLWAY
3) HOUSE WIRING IS AN UNGROUNDED SYSTEM USE ONLY 2 PRONG RECEPTS, UNLESS PROTECTED BY GFCI
4) GFCI PROTECTION REQUIRED FOR KIT RECEPTS, COUNTER TOP ONLY
5) SECURE PLASTIC CONDUIT DRYER
6) ALL A/C UNITS TO BE HARD WIRED, CORDS NOT APPROVED FOR EXTERIOR, ON PROTECTED USE
7) ROMEX EXPOSED EAST SIDE EXT. LIGHT

Completed Inspections

Permit Status: Expired
Permit Number: T08EL01935
Permit Description: RECONNECT:ELECTRIC
Total Completed Inspections - 2
Date Description Inspector Results Comments
11/07/2008 TEP CLEARANCE - PM JWEATHER Approved RECN CLEARED PER W. NORTH
11/07/2008 ELECTRIC - RECONNECT WNORTH Approved IVRS - Inspection :*

Documents

File Name Document Type  
None DOCUMENTS VIEW