Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUND WIRE CUT OFF AND REMOVED AT SERVICE PANEL, INSTALL NEW GRD WIRE AND H20 BOND 2) NEED WORKING SMOKE DETECTORS IN EACH BEDROOM AND ONE IN HALLWAY 3) HOUSE WIRING IS AN UNGROUNDED SYSTEM USE ONLY 2 PRONG RECEPTS, UNLESS PROTECTED BY GFCI 4) GFCI PROTECTION REQUIRED FOR KIT RECEPTS, COUNTER TOP ONLY 5) SECURE PLASTIC CONDUIT DRYER 6) ALL A/C UNITS TO BE HARD WIRED, CORDS NOT APPROVED FOR EXTERIOR, ON PROTECTED USE 7) ROMEX EXPOSED EAST SIDE EXT. LIGHT |