Permit: T08EL01062
Permit Details
Apply Date:
06/11/2008
Applicant:
STURGEON ELECTRIC COMPANY,*C
Description:
ELECTRICAL RECONNECT (APA)
Contractors:
- STURGEON ELECTRIC COMPANY,*C
Outstanding Activity Conditions
Permit Number - T08EL01062
Permit Status: Final
Permit Description: ELECTRICAL RECONNECT (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 06/11/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T08EL01062
Permit Description: ELECTRICAL RECONNECT (APA)
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/23/2008 | ELECTRIC - RECONNECT | RFREIDIN | Approved | IVRS - Inspection :* |
| 06/24/2008 | TEP CLEARANCE - AM | JWEATHER | Approved | RECN CLEARED PER R. FREIDINGER |
| 10/01/2008 | ELECTRIC - FINAL | RFREIDIN | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1) WHAT ARE SINGLE 30 AMP BREAKERS FOR WHAT CIRCUIT ? 30 AMP BREAKERS #12 WIRE TWO TOTAL 2) #14 WIRE ON 20 AMP BREAKERS 3) FROM 1ST INSPECTION PUT ROMEX SPLICE AT FRONT PORCH IN A J-BOX, GRD WIRE IS CUT OFF AT FLOOR LIGHT 4) NEED NO-LUX ANTI/CORROSION ON AL. CONDUCTORS AT BREAKERS 5) COLOR CODE I.D. HOT WIRES IN SERVICE PANEL 6) NEED GFCI PROTECTION RECEPT FRONT PORCH, WITH BUBBLE COVER 7) TWO FUSES IN A/C HEATER DISCONNECT ONE IS 45, 60 AMP LABEL ON UNIT IS NOT LEDGIABLE ? |
| 02/19/2009 | PERMIT FINALED | JWEATHER | Approved |