Permit Details

Status:
Final
Type:
SINGLE FAMILY OTHER
Address:
7250 E 45TH ST
Address NEW:
7250 E 45TH ST
Apply Date:
06/11/2008
Applicant:
STURGEON ELECTRIC COMPANY,*C
Description:
ELECTRICAL RECONNECT (APA)
Contractors:
  • STURGEON ELECTRIC COMPANY,*C

Outstanding Activity Conditions

Permit Number - T08EL01062
Permit Status: Final
Permit Description: ELECTRICAL RECONNECT (APA)
Total Outstanding Activity Conditions - 1
Date Name
06/11/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T08EL01062
Permit Description: ELECTRICAL RECONNECT (APA)
Total Completed Inspections - 4
Date Description Inspector Results Comments
06/23/2008 ELECTRIC - RECONNECT RFREIDIN Approved IVRS - Inspection :*
06/24/2008 TEP CLEARANCE - AM JWEATHER Approved RECN CLEARED PER R. FREIDINGER
10/01/2008 ELECTRIC - FINAL RFREIDIN Approved IVRS - Inspection :
See detailed listing on site.| 999*
1) WHAT ARE SINGLE 30 AMP BREAKERS FOR WHAT CIRCUIT ?
30 AMP BREAKERS #12 WIRE TWO TOTAL
2) #14 WIRE ON 20 AMP BREAKERS
3) FROM 1ST INSPECTION PUT ROMEX SPLICE AT FRONT PORCH IN A J-BOX, GRD WIRE IS CUT OFF AT FLOOR LIGHT
4) NEED NO-LUX ANTI/CORROSION ON AL. CONDUCTORS AT BREAKERS
5) COLOR CODE I.D. HOT WIRES IN SERVICE PANEL
6) NEED GFCI PROTECTION RECEPT FRONT PORCH, WITH BUBBLE COVER
7) TWO FUSES IN A/C HEATER DISCONNECT ONE IS 45, 60 AMP LABEL ON UNIT IS NOT LEDGIABLE ?
02/19/2009 PERMIT FINALED JWEATHER Approved