Permit: T08EL01062

Parcel: 136343830


Addresses:

7250 E 45TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/18/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/01/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WHAT ARE SINGLE 30 AMP BREAKERS FOR WHAT CIRCUIT ?
30 AMP BREAKERS #12 WIRE TWO TOTAL
2) #14 WIRE ON 20 AMP BREAKERS
3) FROM 1ST INSPECTION PUT ROMEX SPLICE AT FRONT PORCH IN A J-BOX, GRD WIRE IS CUT OFF AT FLOOR LIGHT
4) NEED NO-LUX ANTI/CORROSION ON AL. CONDUCTORS AT BREAKERS
5) COLOR CODE I.D. HOT WIRES IN SERVICE PANEL
6) NEED GFCI PROTECTION RECEPT FRONT PORCH, WITH BUBBLE COVER
7) TWO FUSES IN A/C HEATER DISCONNECT ONE IS 45, 60 AMP LABEL ON UNIT IS NOT LEDGIABLE ?
09/08/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXTERIOR OUTLET NOT GFCI PROTECTED PER #2 FROM PREVIOUS INSP. UNDER CARPORT, BY POOL EQUIPMENT AND ANY OTHERS
2) COMPLETE #5 ABOVE
3) GATES TO BE SECURED OTHER THEN CONCRETE BLOCKS
06/23/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING SMOKE DETECTORS
2) OPEN SPLICES EXT. LIGHTING TO BE ON GFCI
3) LOCATE DISHWASHER RECEPT
4) EXHAUST FAN MISSING MASTER BATH
5) SERVICE PANEL #10 CU. ON TWO SEPERATE 30 AMP BREAKERS ? ALL BREAKERS IN PANEL TO BE MURRAY/BRYANT TYPE
6) I WILL REPORT SWIMMING POOL SITUATION TO PROPER DEPT. FOR FOUL WATER AND UNSECURED GATES