Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/18/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/01/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WHAT ARE SINGLE 30 AMP BREAKERS FOR WHAT CIRCUIT ? 30 AMP BREAKERS #12 WIRE TWO TOTAL 2) #14 WIRE ON 20 AMP BREAKERS 3) FROM 1ST INSPECTION PUT ROMEX SPLICE AT FRONT PORCH IN A J-BOX, GRD WIRE IS CUT OFF AT FLOOR LIGHT 4) NEED NO-LUX ANTI/CORROSION ON AL. CONDUCTORS AT BREAKERS 5) COLOR CODE I.D. HOT WIRES IN SERVICE PANEL 6) NEED GFCI PROTECTION RECEPT FRONT PORCH, WITH BUBBLE COVER 7) TWO FUSES IN A/C HEATER DISCONNECT ONE IS 45, 60 AMP LABEL ON UNIT IS NOT LEDGIABLE ? |
|
| 09/08/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXTERIOR OUTLET NOT GFCI PROTECTED PER #2 FROM PREVIOUS INSP. UNDER CARPORT, BY POOL EQUIPMENT AND ANY OTHERS 2) COMPLETE #5 ABOVE 3) GATES TO BE SECURED OTHER THEN CONCRETE BLOCKS |
|
| 06/23/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING SMOKE DETECTORS 2) OPEN SPLICES EXT. LIGHTING TO BE ON GFCI 3) LOCATE DISHWASHER RECEPT 4) EXHAUST FAN MISSING MASTER BATH 5) SERVICE PANEL #10 CU. ON TWO SEPERATE 30 AMP BREAKERS ? ALL BREAKERS IN PANEL TO BE MURRAY/BRYANT TYPE 6) I WILL REPORT SWIMMING POOL SITUATION TO PROPER DEPT. FOR FOUL WATER AND UNSECURED GATES |