Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address:
605 N 4TH AV
Address NEW:
605 N 4TH AV
Apply Date:
05/15/2008
Applicant:
UTE GASCETO
Description:
GENERAL REPAIR:REPLACE 3 METER SERVICE DISCONNECTS
Contractors:
  • STARK ELECTRIC INC ,

Permit Reviews

Permit Number - T08EL00867
Permit Status: Expired
Permit Description: GENERAL REPAIR:REPLACE 3 METER SERVICE DISCONNECTS
Start Date Submittal Complete Date Status  
05/15/2008 ELECTRICAL 05/15/2008 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T08EL00867
Permit Status: Expired
Permit Description: GENERAL REPAIR:REPLACE 3 METER SERVICE DISCONNECTS
Total Outstanding Activity Conditions - 1
Date Name
05/15/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T08EL00867
Permite Description: GENERAL REPAIR:REPLACE 3 METER SERVICE DISCONNECTS
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
05/16/2008 ELECTRIC - SERVICE UPGRADE N/A Partial Approval IVRS - Inspection :*
05/16/2008 ELECTRIC - FINAL N/A Partial Approval IVRS - Inspection :*
1) NEED MIN. #4 ? BOND FOR 2/0 SERVICE RACEWAY NEC 250.102 C
2) DRIVE RODS FLUSH NEC 250.536
3) NEED SECOND GROUND ROD NEC 250.56
4) BOND ALL GAS PIPES NEC 250.104 B
5) RECONNECT OTHER SERVICES GROUND TAPS NEC 250.64 D

Completed Inspections

Permit Status: Expired
Permit Number: T08EL00867
Permit Description: GENERAL REPAIR:REPLACE 3 METER SERVICE DISCONNECTS
Total Completed Inspections - 1
Date Description Inspector Results Comments
05/19/2008 TEP CLEARANCE - AM JWEATHER Approved RECN FOR 605, 609 & 611 N. 4TH AVE., ALL METERS PER C. CLEMENS

Documents

File Name Document Type  
None DOCUMENTS VIEW