Permit: T08EL00867
Permit Details
Apply Date:
05/15/2008
Applicant:
UTE GASCETO
Description:
GENERAL REPAIR:REPLACE 3 METER SERVICE DISCONNECTS
Contractors:
- STARK ELECTRIC INC ,
Permit Reviews
Permit Number - T08EL00867
Permit Status: Expired
Permit Description: GENERAL REPAIR:REPLACE 3 METER SERVICE DISCONNECTS
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 05/15/2008 | ELECTRICAL | 05/15/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T08EL00867
Permit Status: Expired
Permit Description: GENERAL REPAIR:REPLACE 3 METER SERVICE DISCONNECTS
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/15/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T08EL00867
Permite Description: GENERAL REPAIR:REPLACE 3 METER SERVICE DISCONNECTS
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2008 | ELECTRIC - SERVICE UPGRADE | N/A | Partial Approval | IVRS - Inspection :* |
| 05/16/2008 | ELECTRIC - FINAL | N/A | Partial Approval | IVRS - Inspection :* 1) NEED MIN. #4 ? BOND FOR 2/0 SERVICE RACEWAY NEC 250.102 C 2) DRIVE RODS FLUSH NEC 250.536 3) NEED SECOND GROUND ROD NEC 250.56 4) BOND ALL GAS PIPES NEC 250.104 B 5) RECONNECT OTHER SERVICES GROUND TAPS NEC 250.64 D |
Completed Inspections
Permit Status: Expired
Permit Number: T08EL00867
Permit Description: GENERAL REPAIR:REPLACE 3 METER SERVICE DISCONNECTS
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/19/2008 | TEP CLEARANCE - AM | JWEATHER | Approved | RECN FOR 605, 609 & 611 N. 4TH AVE., ALL METERS PER C. CLEMENS |