Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED MIN. #4 ? BOND FOR 2/0 SERVICE RACEWAY NEC 250.102 C 2) DRIVE RODS FLUSH NEC 250.536 3) NEED SECOND GROUND ROD NEC 250.56 4) BOND ALL GAS PIPES NEC 250.104 B 5) RECONNECT OTHER SERVICES GROUND TAPS NEC 250.64 D |