Permit: T08EL00111
Permit Details
Apply Date:
01/22/2008
Applicant:
MARK DAWSON
Description:
REPL LIKE FOR LIKE SERVICE SWITCH GEAR
Contractors:
- DAWSON ELECTRIC L L C
Permit Reviews
Permit Number - T08EL00111
Permit Status: Final
Permit Description: REPL LIKE FOR LIKE SERVICE SWITCH GEAR
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 07/31/2008 | ELECTRICAL | 07/31/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T08EL00111
Permit Status: Final
Permit Description: REPL LIKE FOR LIKE SERVICE SWITCH GEAR
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 01/22/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T08EL00111
Permit Description: REPL LIKE FOR LIKE SERVICE SWITCH GEAR
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/06/2008 | ELECTRIC - PROGRESS | RJIROUDE | Approved | IVRS - Inspection :* 1) INSTALL PROTECTION AROUND CONDUCTORS WHERE PASSING THRU SECTIONS ADN WHERE CONTRACTORS ARE UP AGAINST ANY METAL 2) NEED PANEL DIRECTIVES 3) PLAN CALLS FOR NEW PANEL TO HAVE 300 AMP MIN 4) INSTALL FUSES IN DISCONNECTS AND RECALL AFTER POWER ON 5) PROVIDE LETTER OF TORQUE |
| 08/06/2008 | ELECTRIC - FINAL | RJIROUDE | Approved | IVRS - Inspection :* |
| 08/07/2008 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER R. JIROUDEK |