Permit: T08EL00111

Parcel: 13336008R


Addresses:

700 N BONANZA AV


Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Permit Number - T08EL00111

Inspection Description - ELECTRIC - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
06/05/2009 ELECTRIC - PROGRESS Approved
04/16/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
08/06/2008 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) INSTALL PROTECTION AROUND CONDUCTORS WHERE PASSING THRU SECTIONS ADN WHERE CONTRACTORS ARE UP AGAINST ANY METAL
2) NEED PANEL DIRECTIVES
3) PLAN CALLS FOR NEW PANEL TO HAVE 300 AMP MIN
4) INSTALL FUSES IN DISCONNECTS AND RECALL AFTER POWER ON
5) PROVIDE LETTER OF TORQUE
07/23/2008 ELECTRIC - PROGRESS Denied 1. NEED TO HAVE PLANS FOR SCOPE OF WORK. CALLED LEERAY LOOKED UP WORK & SCOPE OF WORK WAS STATED TO CITY TO BE 200 AMP SERVICE
2. NEED TO INSTALL NEW GROUNDING ELECTRODE SYSTEM
NEED TO BOND GAS AND WATER
3. FEEDERS NEED TO ENTER SWITCH BASED IN SECTION SERVED
4. CANNOT HAVE FEEDERS IN SERVICE ENTRANCE SECTION
5. NEED TO PROVIDE LETTER OF TORQUE
6. THIS NEEDS TO BE STRAIGHTENED OUT DOWNTOWN WITH LEE RAY HANLY
7. SWITCH GEAR TO BE SECURED PER INSTRUCTIONS
8. CANNOT LOCATE MAIN BONDING JUMPER