Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T08EL00111
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/05/2009 | ELECTRIC - PROGRESS | Approved | ||
| 04/16/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 08/06/2008 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) INSTALL PROTECTION AROUND CONDUCTORS WHERE PASSING THRU SECTIONS ADN WHERE CONTRACTORS ARE UP AGAINST ANY METAL 2) NEED PANEL DIRECTIVES 3) PLAN CALLS FOR NEW PANEL TO HAVE 300 AMP MIN 4) INSTALL FUSES IN DISCONNECTS AND RECALL AFTER POWER ON 5) PROVIDE LETTER OF TORQUE |
|
| 07/23/2008 | ELECTRIC - PROGRESS | Denied | 1. NEED TO HAVE PLANS FOR SCOPE OF WORK. CALLED LEERAY LOOKED UP WORK & SCOPE OF WORK WAS STATED TO CITY TO BE 200 AMP SERVICE 2. NEED TO INSTALL NEW GROUNDING ELECTRODE SYSTEM NEED TO BOND GAS AND WATER 3. FEEDERS NEED TO ENTER SWITCH BASED IN SECTION SERVED 4. CANNOT HAVE FEEDERS IN SERVICE ENTRANCE SECTION 5. NEED TO PROVIDE LETTER OF TORQUE 6. THIS NEEDS TO BE STRAIGHTENED OUT DOWNTOWN WITH LEE RAY HANLY 7. SWITCH GEAR TO BE SECURED PER INSTRUCTIONS 8. CANNOT LOCATE MAIN BONDING JUMPER |