Description:
upgrade to 200 amp underground service
Contractors:
  • ELECTRICAL WIZARD

Outstanding Activity Conditions

Permit Number - T08EL00083
Permit Status: Expired
Permit Description: upgrade to 200 amp underground service
Total Outstanding Activity Conditions - 1
Date Name
01/15/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T08EL00083
Permite Description: upgrade to 200 amp underground service
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
01/24/2008 ELECTRIC - INTERMEDIATE N/A Partial Approval IVRS - Inspection :*
1) OK GROUND RODS
2) OK GAS AND WATER BOND
3) RECALL AFTER SWING OVER COMPLETE
02/20/2008 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE OLD MAST AND PATCH ROOF
2. REGROUND TELCO & CATV
3. GROUND J-BOX WITH EQUIPMENT GROUND
4. NEED PROTECTIVE BUSHING #4 & LARGER CONDUCTOR
(OLD FEEDER INTO J-BOX)
5. MINIMUM SIZE EQUIPMENT GROUND
FOR 100 AMP CKT IS #8 CU
6. WIRE NUTS TO BE USED FOR # & SIZE OF CONDUCTORS LISTED FOR
7. EMT TO BE SECURED WITHIN 36" OF ENCLOSURES
8. SEALING LOCKNUT NOT SEALING TOP OF SERVICE - CAN SEE DAYLIGHT THROUGH OPENING

Completed Inspections

Permit Status: Expired
Permit Number: T08EL00083
Permit Description: upgrade to 200 amp underground service
Total Completed Inspections - 1
Date Description Inspector Results Comments
01/25/2008 TEP CLEARANCE - AM JWEATHER Approved INCR CLEARED PER R. JIROUDEK