Permit: T08EL00083

Parcel: 125092290


Addresses:

237 N HARRIS AV

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/20/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE OLD MAST AND PATCH ROOF
2. REGROUND TELCO & CATV
3. GROUND J-BOX WITH EQUIPMENT GROUND
4. NEED PROTECTIVE BUSHING #4 & LARGER CONDUCTOR
(OLD FEEDER INTO J-BOX)
5. MINIMUM SIZE EQUIPMENT GROUND
FOR 100 AMP CKT IS #8 CU
6. WIRE NUTS TO BE USED FOR # & SIZE OF CONDUCTORS LISTED FOR
7. EMT TO BE SECURED WITHIN 36" OF ENCLOSURES
8. SEALING LOCKNUT NOT SEALING TOP OF SERVICE - CAN SEE DAYLIGHT THROUGH OPENING
02/14/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
NO ACCESS, DOGS IN YARD
NO ANSWER @ DOOR