Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/20/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE OLD MAST AND PATCH ROOF 2. REGROUND TELCO & CATV 3. GROUND J-BOX WITH EQUIPMENT GROUND 4. NEED PROTECTIVE BUSHING #4 & LARGER CONDUCTOR (OLD FEEDER INTO J-BOX) 5. MINIMUM SIZE EQUIPMENT GROUND FOR 100 AMP CKT IS #8 CU 6. WIRE NUTS TO BE USED FOR # & SIZE OF CONDUCTORS LISTED FOR 7. EMT TO BE SECURED WITHIN 36" OF ENCLOSURES 8. SEALING LOCKNUT NOT SEALING TOP OF SERVICE - CAN SEE DAYLIGHT THROUGH OPENING |
|
| 02/14/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* NO ACCESS, DOGS IN YARD NO ANSWER @ DOOR |