Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T08CM03710
Permit Details
Apply Date:
11/18/2008
Applicant:
N/A
Description:
TI: CHURCH NEW C OF O, CHANGE OF OCCUPANCY
Architects:
- HAGEDON, BRIAN GEORGE
Contractors:
- VALLARTA CONSTRUCTION INC
Permit Reviews
Permit Number - T08CM03710
Permit Status: C of o
Permit Description: TI: CHURCH NEW C OF O, CHANGE OF OCCUPANCY
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
11/18/2008 | COMMERCIAL TI | 11/18/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T08CM03710
Permit Status: C of o
Permit Description: TI: CHURCH NEW C OF O, CHANGE OF OCCUPANCY
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
11/18/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T08CM03710
Permit Description: TI: CHURCH NEW C OF O, CHANGE OF OCCUPANCY
Total Completed Inspections - 17
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/18/2008 | BUILDING ABOVE CEILING | JBURGE | Approved | IVRS - Inspection :* EXISTING SYSTEM TO REMAIN |
12/18/2008 | FRAMING | JBURGE | Approved | IVRS - Inspection :* ALL AREAS IN #209 |
12/18/2008 | FIRE SPKLR - FINAL | CSCHULTZ | Approved | |
12/22/2008 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* WILL CHECK CONDENSATE ON FINAL |
12/22/2008 | SHEET ROCK NAILING | JBURGE | Approved | IVRS - Inspection :* NORTH WALLS ABOVE CEILING IN CLASSROOM #213 OK TO TAPE THROUGHOUT |
12/31/2008 | MECHANICAL - FINAL | MRAMBER | Approved | IVRS - Inspection :* 1) PROVIDE CONDENSATE PIPING PER PLAN AND PROVIDE PROPER SUPPORT 2) RTU DUCT SEALER NOT COMPLETE 3) SEAL OPENINGS IN OSA TAPS 4) TIGHTEN L.V. CONNECTIONS 5) PROVIDE COPY OF AIR BALANCE REPORT. SEE BLDG INSPECTOR FOR TEMP C OF O 6) TERMINATE 1 1/4" CONDENSATE PIPING AT AN APPROVED LOCATION |
12/31/2008 | BUILDING - FINAL | GDABBS | Approved | IVRS - Inspection :* 1) NEED TRADE FINALS BEFORE BLDG FINAL |
12/31/2008 | FIRE - FINAL | CSCHULTZ | Approved | |
12/31/2008 | ELECTRIC - ABOVE CEILING | DSANTACR | Approved | IVRS - Inspection :* |
12/31/2008 | ELECTRIC - INTERMEDIATE | DSANTACR | Approved | IVRS - Inspection :* |
12/31/2008 | ELECTRIC - FINAL | DSANTACR | Approved | IVRS - Inspection :* |
01/02/2009 | NPPO - FINAL | ACONNOR | Approved | N/A |
01/02/2009 | LANDSCAPE - FINAL | ACONNOR | Approved | N/A |
01/02/2009 | RIGHT OF WAY - FINAL | PWHIDDON | Approved | PER EMAIL |
01/02/2009 | ENGINEERING - FINAL | NKALAHAR | Approved | INTERIOR ONLY PER STAMP 11/18 BIANCA |
01/07/2009 | PERMIT FINALED | LJACKSON | Approved | |
01/07/2009 | SIGN - FINAL | HTHRALL | Approved | PERMITTED BANNER AND DOOR SIGN. CLEAR TO ISSUE C OF O |