Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/02/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/31/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE CONDENSATE PIPING PER PLAN AND PROVIDE PROPER SUPPORT 2) RTU DUCT SEALER NOT COMPLETE 3) SEAL OPENINGS IN OSA TAPS 4) TIGHTEN L.V. CONNECTIONS 5) PROVIDE COPY OF AIR BALANCE REPORT. SEE BLDG INSPECTOR FOR TEMP C OF O 6) TERMINATE 1 1/4" CONDENSATE PIPING AT AN APPROVED LOCATION |