Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. ONLY SERVICE CONDUCTORS IN SERVICE DISCONNECT 2. CANNOT STACK LUGS 3. NEED SIGNAGE PER 703.8 4. SEPARATE GROUNDS & NEUTRALS AT SUB-PANEL 5. NEED SUPPLEMENTARY GROUNDING ELECTRODE 6. SECURE RECEPTACLE BOX INSIDE OF GENERATOR ENCLOSURE 7. UNCOVER CONDUITS AT GENERATOR TO INSPECT 8. SUPPORT CONDUITS UNDER TRANSFER SWITCH 9. VERIFY GROUND RING AT GENERATOR PAD 10. TRANSFER SWITCH DOES NOT APPEAR TO BE AS PER PLANS -- NO FUSES OR SERIES LIGHTING 11. INSTALL CIRCUITS AS PER PLANS |
|
| 01/05/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL NEW WORK TO BE EXPOSED 2. EQUIPMENT TO BE OPEN FOR INSPECTION |