Permit: T08CM02888

Parcel: 129133340


Addresses:

2419 S PARK AV

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/06/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. ONLY SERVICE CONDUCTORS IN SERVICE DISCONNECT
2. CANNOT STACK LUGS
3. NEED SIGNAGE PER 703.8
4. SEPARATE GROUNDS & NEUTRALS AT SUB-PANEL
5. NEED SUPPLEMENTARY GROUNDING ELECTRODE
6. SECURE RECEPTACLE BOX INSIDE OF GENERATOR ENCLOSURE
7. UNCOVER CONDUITS AT GENERATOR TO INSPECT
8. SUPPORT CONDUITS UNDER TRANSFER SWITCH
9. VERIFY GROUND RING AT GENERATOR PAD
10. TRANSFER SWITCH DOES NOT APPEAR TO BE AS PER PLANS -- NO FUSES OR SERIES LIGHTING
11. INSTALL CIRCUITS AS PER PLANS
01/05/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ALL NEW WORK TO BE EXPOSED
2. EQUIPMENT TO BE OPEN FOR INSPECTION