Permit: T08CM02791
Permit Details
Apply Date:
08/15/2008
Applicant:
N/A
Description:
REPLACE: 23 A/C UNITS (T08DV05154)
Contractors:
- B A ELECTRIC *T
- BALLARD A C AND HEATING L L C
Permit Reviews
Permit Number - T08CM02791
Permit Status: Final
Permit Description: REPLACE: 23 A/C UNITS (T08DV05154)
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
08/15/2008 | OTHER | 09/25/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T08CM02791
Permit Status: Final
Permit Description: REPLACE: 23 A/C UNITS (T08DV05154)
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
08/15/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T08CM02791
Permit Description: REPLACE: 23 A/C UNITS (T08DV05154)
Total Completed Inspections - 6
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/14/2008 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1. I.D. CIRCUIT BREAKERS TO AC UNITS 2. SUPPORT PVC ON ROOF EVERY 4' 3. PAINT ALL EXPOSED PVC W/LATEX PAINT 4. DO NOT USE WHITE WIRE TO POWER A/C UNITS 5. SUPPORT ELEC. CONDUITS ON ROOF 6. STRAP ALL ROMEX IN ATTICS 7. MARK UNIT DATA PLATES AND FUSE ACCORDINGLY 8. PROVIDE GFI SERVICE RECEPTACLES ON ROOF 9. PROVIDE ROOF JACKS AT CONDENSATE PENETRATIONS 10. SEAL HOLES IN CURBS 11. TERMINATE CONDENSATE DRAINS TO DIRT CODE MANAGER ENTER FROM FAIRMOUNT |
11/14/2008 | BUILDING - FINAL | JBURGE | Approved | IVRS - Inspection :* NO STRUCTURAL @ THIS SITE |
11/14/2008 | ELECTRIC - UNDERGROUND | RMORENO | Approved | IVRS - Inspection :* |
01/16/2009 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE OK FOR FINAL |
01/21/2009 | ELECTRIC - FINAL | RMORENO | Approved | IVRS - Inspection :* |
01/22/2009 | PERMIT FINALED | BFLORES | Approved |