Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/16/2009 | MECHANICAL - INTERMEDIATE | Approved | ||
| 11/14/2008 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. I.D. CIRCUIT BREAKERS TO AC UNITS 2. SUPPORT PVC ON ROOF EVERY 4' 3. PAINT ALL EXPOSED PVC W/LATEX PAINT 4. DO NOT USE WHITE WIRE TO POWER A/C UNITS 5. SUPPORT ELEC. CONDUITS ON ROOF 6. STRAP ALL ROMEX IN ATTICS 7. MARK UNIT DATA PLATES AND FUSE ACCORDINGLY 8. PROVIDE GFI SERVICE RECEPTACLES ON ROOF 9. PROVIDE ROOF JACKS AT CONDENSATE PENETRATIONS 10. SEAL HOLES IN CURBS 11. TERMINATE CONDENSATE DRAINS TO DIRT CODE MANAGER ENTER FROM FAIRMOUNT |