Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T08CM02146
Permit Details
Apply Date:
06/17/2008
Applicant:
N/A
Description:
CONSTRUCTION TRAILER W/ELECTRIC
Contractors:
- F N F CONSTRUCTION INC ,
Permit Reviews
Permit Number - T08CM02146
Permit Status: Expired
Permit Description: CONSTRUCTION TRAILER W/ELECTRIC
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
06/17/2008 | COMMERCIAL-BLDG/FIRE/ZONING/ENG | 07/14/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T08CM02146
Permit Status: Expired
Permit Description: CONSTRUCTION TRAILER W/ELECTRIC
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
06/17/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T08CM02146
Permite Description: CONSTRUCTION TRAILER W/ELECTRIC
Total Outstanding Inspections - 2
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/30/2008 | ELECTRIC - TEMPORARY POLE | N/A | Not ready for Inspection | IVRS - Inspection :* |
08/04/2008 | ELECTRIC - FINAL | N/A | Partial Approval | IVRS - Inspection :* 1) GROUND RODS TO BE DRIVEN 2) INSTALL GROUNDING ELECTRODE CONDUCTOR TO EACH PANEL NOT FROM ONE PANEL TO THE OTHER. TO BE CONTINOUS FROM ELECTRODE TO PANEL 3) BACK FED BREAKERS TO BE MECHANICALLY SECURED TO PANEL 4) SPLICES IN UNDERGROUND ? HOLE BOXES TO BE LISTED FOR WET LOCATION |
Completed Inspections
Permit Status: Expired
Permit Number: T08CM02146
Permit Description: CONSTRUCTION TRAILER W/ELECTRIC
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/05/2008 | TEP CLEARANCE - AM | JWEATHER | Approved | ECO CLEARED PER R. JIROUDEK |