Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM02146
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/04/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) GROUND RODS TO BE DRIVEN 2) INSTALL GROUNDING ELECTRODE CONDUCTOR TO EACH PANEL NOT FROM ONE PANEL TO THE OTHER. TO BE CONTINOUS FROM ELECTRODE TO PANEL 3) BACK FED BREAKERS TO BE MECHANICALLY SECURED TO PANEL 4) SPLICES IN UNDERGROUND ? HOLE BOXES TO BE LISTED FOR WET LOCATION |
|