Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T08CM02146

Parcel: 14044007B

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM02146

Inspection Description - ELECTRIC - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
08/04/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) GROUND RODS TO BE DRIVEN
2) INSTALL GROUNDING ELECTRODE CONDUCTOR TO EACH PANEL NOT FROM ONE PANEL TO THE OTHER. TO BE CONTINOUS FROM ELECTRODE TO PANEL
3) BACK FED BREAKERS TO BE MECHANICALLY SECURED TO PANEL
4) SPLICES IN UNDERGROUND ? HOLE BOXES TO BE LISTED FOR WET LOCATION
07/30/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. OK GROUND RODS @ SERVICE
2. NEED PROPER CLEARANCE TO GROUND ON SERVICE CONDUCTORS
3. OK TO BACKFILL TO FIRST TRAILER
4. FINISH WORK & RECALL WHEN READY