Permit: T08CM01143
Permit Details
Apply Date:
04/10/2008
Applicant:
N/A
Description:
NEW: ELECTRICAL GROUND CABINET AND 6' WALL; COMMERCIAL. NEW UTILITY POLE (64') TO REPLACE EXISTING POLE
Contractors:
- HERITAGE NATIONAL CORPORATION
Permit Reviews
Permit Number - T08CM01143
Permit Status: Expired
Permit Description: NEW: ELECTRICAL GROUND CABINET AND 6' WALL; COMMERCIAL.
NEW UTILITY POLE (64') TO REPLACE EXISTING POLE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 04/10/2008 | COMMERCIAL NEW | 04/10/2008 | COMPLETED |
| 05/07/2008 | RESUBMITTAL | 06/05/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T08CM01143
Permit Status: Expired
Permit Description: NEW: ELECTRICAL GROUND CABINET AND 6' WALL; COMMERCIAL.
NEW UTILITY POLE (64') TO REPLACE EXISTING POLE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 04/10/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T08CM01143
Permite Description: NEW: ELECTRICAL GROUND CABINET AND 6' WALL; COMMERCIAL.
NEW UTILITY POLE (64') TO REPLACE EXISTING POLE
Total Outstanding Inspections - 5
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| BUILDING - FINAL | N/A | Not Inspected | ||
| 06/17/2008 | ELECTRIC - UNDERGROUND | N/A | Partial Approval | IVRS - Inspection :* OK GROUND RING AND FEEDER RACEWAY & PHONE RACEWAY |
| 06/26/2008 | ELECTRIC - TEMPORARY SERVICE | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. IDENTIFY "SERVICE DISCONNECT" AS SUCH - NEC 230.72B 2. BONDING CONDUCTOR FOR METER TO DISCONNECT RACEWAY NOT CORRECTLY SIZED - NEC 250.102C 3. GROUNDING ELECTRODE CONDUCTOR TO CONNECT DIRECTLY TO GROUNDED CONDUCTOR OR VIA A MAIN BONDING JUMPER - NEC 250.24A 4. INSTALL FEEDERS TO PANEL 5. INSTALL FUSES 6. TIGHTEN METER BASE BOND SCREW 7. STRAP FLEX UP WALL TO DISCONNECT - NEC 356.30 8. TIGHTEN ALL CONNECTIONS 9. SERVICE WILL NOT BE ENERGIZED BEFORE LOADS ARE READY 10. CALL 02050 "CABLE DROP" NOT 02060 "TEMPORARY SERVICE" |
| 08/28/2008 | ELECTRIC - CABLE DROP | N/A | Partial Approval | IVRS - Inspection :* |
| 08/29/2008 | ELECTRIC - FINAL | N/A | Not ready for Inspection | IVRS - Inspection :* CANCELED |
Completed Inspections
Permit Status: Expired
Permit Number: T08CM01143
Permit Description: NEW: ELECTRICAL GROUND CABINET AND 6' WALL; COMMERCIAL.
NEW UTILITY POLE (64') TO REPLACE EXISTING POLE
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2008 | TEP CLEARANCE - AM | BFLORES | Approved | TEC PER R.HOLLANDER |