Permit Details

Status:
Expired
Type:
COMMERCIAL ADDITION
Address:
1802 E ROGER RD
Address NEW:
1802 E ROGER RD
Apply Date:
04/10/2008
Applicant:
N/A
Description:
NEW: ELECTRICAL GROUND CABINET AND 6' WALL; COMMERCIAL. NEW UTILITY POLE (64') TO REPLACE EXISTING POLE
Contractors:
  • HERITAGE NATIONAL CORPORATION

Permit Reviews

Permit Number - T08CM01143
Permit Status: Expired
Permit Description: NEW: ELECTRICAL GROUND CABINET AND 6' WALL; COMMERCIAL. NEW UTILITY POLE (64') TO REPLACE EXISTING POLE
Start Date Submittal Complete Date Status  
04/10/2008 COMMERCIAL NEW 04/10/2008 COMPLETED Review Details
05/07/2008 RESUBMITTAL 06/05/2008 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T08CM01143
Permit Status: Expired
Permit Description: NEW: ELECTRICAL GROUND CABINET AND 6' WALL; COMMERCIAL. NEW UTILITY POLE (64') TO REPLACE EXISTING POLE
Total Outstanding Activity Conditions - 1
Date Name
04/10/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T08CM01143
Permite Description: NEW: ELECTRICAL GROUND CABINET AND 6' WALL; COMMERCIAL. NEW UTILITY POLE (64') TO REPLACE EXISTING POLE
Total Outstanding Inspections - 5
Last Inspection Date Description Inspector Results Comments
BUILDING - FINAL N/A Not Inspected
06/17/2008 ELECTRIC - UNDERGROUND N/A Partial Approval IVRS - Inspection :*
OK GROUND RING AND FEEDER RACEWAY & PHONE RACEWAY
06/26/2008 ELECTRIC - TEMPORARY SERVICE N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. IDENTIFY "SERVICE DISCONNECT" AS SUCH - NEC 230.72B
2. BONDING CONDUCTOR FOR METER TO DISCONNECT RACEWAY NOT CORRECTLY SIZED - NEC 250.102C
3. GROUNDING ELECTRODE CONDUCTOR TO CONNECT DIRECTLY TO GROUNDED CONDUCTOR OR VIA A MAIN BONDING JUMPER - NEC 250.24A
4. INSTALL FEEDERS TO PANEL
5. INSTALL FUSES
6. TIGHTEN METER BASE BOND SCREW
7. STRAP FLEX UP WALL TO DISCONNECT - NEC 356.30
8. TIGHTEN ALL CONNECTIONS
9. SERVICE WILL NOT BE ENERGIZED BEFORE LOADS ARE READY
10. CALL 02050 "CABLE DROP" NOT 02060 "TEMPORARY SERVICE"
08/28/2008 ELECTRIC - CABLE DROP N/A Partial Approval IVRS - Inspection :*
08/29/2008 ELECTRIC - FINAL N/A Not ready for Inspection IVRS - Inspection :*
CANCELED

Completed Inspections

Permit Status: Expired
Permit Number: T08CM01143
Permit Description: NEW: ELECTRICAL GROUND CABINET AND 6' WALL; COMMERCIAL. NEW UTILITY POLE (64') TO REPLACE EXISTING POLE
Total Completed Inspections - 1
Date Description Inspector Results Comments
08/29/2008 TEP CLEARANCE - AM BFLORES Approved TEC PER R.HOLLANDER

Documents

File Name Document Type  
001__T-1.TIF CONSTRPLANS VIEW
002__LS-1.TIF CONSTRPLANS VIEW
003__C-1.TIF CONSTRPLANS VIEW
004__C-2.TIF CONSTRPLANS VIEW
005__C-3.TIF CONSTRPLANS VIEW
006__E-1.TIF CONSTRPLANS VIEW
007__E-2.TIF CONSTRPLANS VIEW
008__E-3.TIF CONSTRPLANS VIEW
009__S-1.TIF CONSTRPLANS VIEW
None DOCUMENTS VIEW