Inspection Status: Denied
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T08CM01143
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/26/2008 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. IDENTIFY "SERVICE DISCONNECT" AS SUCH - NEC 230.72B 2. BONDING CONDUCTOR FOR METER TO DISCONNECT RACEWAY NOT CORRECTLY SIZED - NEC 250.102C 3. GROUNDING ELECTRODE CONDUCTOR TO CONNECT DIRECTLY TO GROUNDED CONDUCTOR OR VIA A MAIN BONDING JUMPER - NEC 250.24A 4. INSTALL FEEDERS TO PANEL 5. INSTALL FUSES 6. TIGHTEN METER BASE BOND SCREW 7. STRAP FLEX UP WALL TO DISCONNECT - NEC 356.30 8. TIGHTEN ALL CONNECTIONS 9. SERVICE WILL NOT BE ENERGIZED BEFORE LOADS ARE READY 10. CALL 02050 "CABLE DROP" NOT 02060 "TEMPORARY SERVICE" |