Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Apply Date:
03/14/2008
Applicant:
RECORD ENERGY CONCEPTS *C
Description:
SPLIT SYSTEM/AC UNIT & DUCT WORK
Contractors:
  • RECORD ENERGY CONCEPTS *C

Permit Reviews

Permit Number - T08CM00859
Permit Status: Expired
Permit Description: SPLIT SYSTEM/AC UNIT & DUCT WORK
Start Date Submittal Complete Date Status  
03/14/2008 OTHER 03/27/2008 COMPLETED Review Details
04/04/2008 OTHER 04/04/2008 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T08CM00859
Permit Status: Expired
Permit Description: SPLIT SYSTEM/AC UNIT & DUCT WORK
Total Outstanding Activity Conditions - 1
Date Name
03/14/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T08CM00859
Permite Description: SPLIT SYSTEM/AC UNIT & DUCT WORK
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
06/16/2008 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
ON ROOF
1. GROUND FEEDER J-BOX WITH EQUIPMENT GROUND
2. REMOVE PAINT UNDER GROUND LUG IN GUTTER
3. NEED PERMANENT I.D LABELS FOR DISCONNECTS, AND NEED TO BE PROPERLY IDENTIFIED, CONDENSING UNIT DISCONNECT NOT PROPERLY PHASED ON LOAD SIDE
4. NEED GFI PROTECTED SERVICE RECEPTACLE - SEE PLANS
5. PROPERLY RE-IDENTIFY FEEDER AT SWITCH GEAR TO INDICATE NEW LOADS
6. WIRING NOT PER PLAN
7. CORRECTLY IDENTIFY EQUIPMENT PER PLAN

INSIDE
1. STRAP FLEX WITHIN 12" OF ENCLOSURES
2. 2 CONDUCTORS NOT ALLOWED UNDER SAME GROUND LUG INDOOR DISCONNECTS OUTSIDE?

Completed Inspections

Permit Status: Expired
Permit Number: T08CM00859
Permit Description: SPLIT SYSTEM/AC UNIT & DUCT WORK
Total Completed Inspections - 3
Date Description Inspector Results Comments
06/16/2008 MECHANICAL - ABOVE CEILING MRAMBER Approved
06/16/2008 MECHANICAL - INTERMEDIATE MRAMBER Approved
06/16/2008 MECHANICAL - FINAL MRAMBER Approved IVRS - Inspection :*

Documents

File Name Document Type  
T08CM00859_001.TIF CONSTRPLANS VIEW
T08CM00859_002.TIF CONSTRPLANS VIEW
T08CM00859_003.TIF CONSTRPLANS VIEW
T08CM00859_004.TIF CONSTRPLANS VIEW
T08CM00859_005.TIF CONSTRPLANS VIEW
T08CM00859_006.TIF CONSTRPLANS VIEW
T08CM00859_007.TIF CONSTRPLANS VIEW
T08CM00859_008.TIF CONSTRPLANS VIEW
None DOCUMENTS VIEW