Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM00859
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/16/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ON ROOF 1. GROUND FEEDER J-BOX WITH EQUIPMENT GROUND 2. REMOVE PAINT UNDER GROUND LUG IN GUTTER 3. NEED PERMANENT I.D LABELS FOR DISCONNECTS, AND NEED TO BE PROPERLY IDENTIFIED, CONDENSING UNIT DISCONNECT NOT PROPERLY PHASED ON LOAD SIDE 4. NEED GFI PROTECTED SERVICE RECEPTACLE - SEE PLANS 5. PROPERLY RE-IDENTIFY FEEDER AT SWITCH GEAR TO INDICATE NEW LOADS 6. WIRING NOT PER PLAN 7. CORRECTLY IDENTIFY EQUIPMENT PER PLAN INSIDE 1. STRAP FLEX WITHIN 12" OF ENCLOSURES 2. 2 CONDUCTORS NOT ALLOWED UNDER SAME GROUND LUG INDOOR DISCONNECTS OUTSIDE? |