Permit: T08CM00859

Parcel: 117120870


Addresses:

2 E CONGRESS ST 02


Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM00859

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
06/16/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ON ROOF
1. GROUND FEEDER J-BOX WITH EQUIPMENT GROUND
2. REMOVE PAINT UNDER GROUND LUG IN GUTTER
3. NEED PERMANENT I.D LABELS FOR DISCONNECTS, AND NEED TO BE PROPERLY IDENTIFIED, CONDENSING UNIT DISCONNECT NOT PROPERLY PHASED ON LOAD SIDE
4. NEED GFI PROTECTED SERVICE RECEPTACLE - SEE PLANS
5. PROPERLY RE-IDENTIFY FEEDER AT SWITCH GEAR TO INDICATE NEW LOADS
6. WIRING NOT PER PLAN
7. CORRECTLY IDENTIFY EQUIPMENT PER PLAN

INSIDE
1. STRAP FLEX WITHIN 12" OF ENCLOSURES
2. 2 CONDUCTORS NOT ALLOWED UNDER SAME GROUND LUG INDOOR DISCONNECTS OUTSIDE?