Permit: T08CM00737
Permit Details
Apply Date:
03/04/2008
Applicant:
TEMPLETON MAYRA L
Description:
NEW ROOFTOP HVAC SYSTEM WORK DONE PREVIOUSLY W/OUT PERMIT
Permit Reviews
Permit Number - T08CM00737
Permit Status: Expired
Permit Description: NEW ROOFTOP HVAC SYSTEM
WORK DONE PREVIOUSLY W/OUT PERMIT
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 03/04/2008 | RESIDENTIAL BLDG/ZONING-WALKTHRU | 04/23/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T08CM00737
Permit Status: Expired
Permit Description: NEW ROOFTOP HVAC SYSTEM
WORK DONE PREVIOUSLY W/OUT PERMIT
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 03/04/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T08CM00737
Permite Description: NEW ROOFTOP HVAC SYSTEM
WORK DONE PREVIOUSLY W/OUT PERMIT
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/02/2009 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) #8 WIRE GOOD FOR MAX 50 AMPS 2) NEED GROUND WIRE FROM PANEL 3) MAX FUSE SIZE 50 AMPS 4) HARD PIPE REQUIRED IN FURNACE CLOSET 5) SEDIMENT TRAP AND GAS VALVE REQUIRED ON ROOF |
| 04/02/2009 | PLUMBING - GAS PRESS TEST FNL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
| 04/02/2009 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |