Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/02/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) #8 WIRE GOOD FOR MAX 50 AMPS 2) NEED GROUND WIRE FROM PANEL 3) MAX FUSE SIZE 50 AMPS 4) HARD PIPE REQUIRED IN FURNACE CLOSET 5) SEDIMENT TRAP AND GAS VALVE REQUIRED ON ROOF |